How to do AC withstand voltage test for cables?

How to do AC withstand voltage test for cables?

(Summary description)  Due to the large capacity of the cable, the use of traditional power frequency test transformers is bulky, bulky, and high-current working power is not easy to obtain on site. Therefore, series resonance AC withstand voltage test '>AC withstand voltage test equipment is generally used. The input power capacity can be significantly reduced, the weight is reduced, and it is easy to use and transport. In the early stage, the modulated series resonance equipment (50Hz) was mostly used, but there were disadvantages such as poor automation and high noise. Therefore, most of them now use frequency modulation (30-300Hz) series resonance test equipment, which can obtain higher quality (Q value), and has automatic tuning, multiple protections, and low-noise, flexible combination methods (single piece weight is large Down) and other advantages. Based on the relevant technical data at home and abroad, choosing the appropriate test frequency range is a relatively important issue. In this regard, there are some different views and formulations. In terms of the current domestic and foreign formulations, we can conclude that it can be divided into 3 categories: the first category is a wide frequency range of 30-300Hz, 20-300Hz, 1-300Hz; the second category is the power frequency range, 45-65Hz, 45-55Hz; The third category is close to power frequency, 35-75Hz.

How to do AC withstand voltage test for cables?

(Summary description)  Due to the large capacity of the cable, the use of traditional power frequency test transformers is bulky, bulky, and high-current working power is not easy to obtain on site. Therefore, series resonance AC withstand voltage test '>AC withstand voltage test equipment is generally used. The input power capacity can be significantly reduced, the weight is reduced, and it is easy to use and transport. In the early stage, the modulated series resonance equipment (50Hz) was mostly used, but there were disadvantages such as poor automation and high noise. Therefore, most of them now use frequency modulation (30-300Hz) series resonance test equipment, which can obtain higher quality (Q value), and has automatic tuning, multiple protections, and low-noise, flexible combination methods (single piece weight is large Down) and other advantages. Based on the relevant technical data at home and abroad, choosing the appropriate test frequency range is a relatively important issue. In this regard, there are some different views and formulations. In terms of the current domestic and foreign formulations, we can conclude that it can be divided into 3 categories: the first category is a wide frequency range of 30-300Hz, 20-300Hz, 1-300Hz; the second category is the power frequency range, 45-65Hz, 45-55Hz; The third category is close to power frequency, 35-75Hz.

Information
  Due to the large capacity of the cable, the use of traditional power frequency test transformers is bulky, bulky, and high-current working power is not easy to obtain on site. Therefore, series resonance AC withstand voltage test '>AC withstand voltage test equipment is generally used. The input power capacity can be significantly reduced, the weight is reduced, and it is easy to use and transport. In the early stage, the modulated series resonance equipment (50Hz) was mostly used, but there were disadvantages such as poor automation and high noise. Therefore, most of them now use frequency modulation (30-300Hz) series resonance test equipment, which can obtain higher quality (Q value), and has automatic tuning, multiple protections, and low-noise, flexible combination methods (single piece weight is large Down) and other advantages. Based on the relevant technical data at home and abroad, choosing the appropriate test frequency range is a relatively important issue. In this regard, there are some different views and formulations. In terms of the current domestic and foreign formulations, we can conclude that it can be divided into 3 categories: the first category is a wide frequency range of 30-300Hz, 20-300Hz, 1-300Hz; the second category is the power frequency range, 45-65Hz, 45-55Hz; The third category is close to power frequency, 35-75Hz.
  
  (1) Type 1 wide frequency range
  
  The “Test Guidelines” issued by Working Groups 21 and 09 of the International Conference on Large Power Grids suggests that the frequency range is 30-300 Hz. But in fact, lower frequencies also have better equivalence. IEC60840 and IEC62067 draft standards (2001 and 2000) stipulate that 20-300 Hz can be used.
  
  Some foreign manufacturers design series harmonic reactors, and under special circumstances, some have the lowest frequency of 25Hz or 20Hz. Of course, the lower the frequency, the greater the length (capacitance) of the cable under test. However, the reactor core is enlarged, increasing the weight. Individual data show that the 1-300Hz AC test is also equivalent to the power frequency AC test, which shows that the lower frequency limit may be lower in practical applications, for example, less than 20Hz or even 0.1Hz is also feasible. It further shows that in this frequency range, the voltage distribution and dielectric characteristics of the various media inside the insulation are still basically the same.
  
  Is it appropriate for the working frequency to exceed 300Hz? There are reports that as the frequency increases, the loss of the series resonance reactor and the excitation transformer decreases, but the polarization heating of the capacitor medium of the test product must be considered, so the frequency higher than 300Hz is not advisable.
  
  (2) The second category is the power frequency range
  
  The international industrial frequency mainly refers to 50Hz and 60Hz. Therefore, the IEC standard stipulates that the industrial test frequency range for high-voltage insulation is 45-65Hz, and the rated power frequency in my country is 50Hz. GB/T16927.1-1997 stipulates that the power frequency test frequency range is 45-55Hz.
  
  believes that the test voltage of a power frequency power cable must also be a power frequency, which is a conservative view. In view of this problem, it should be emphasized that the purpose of handover and preventive testing is to determine the ability to find insulation defects. As long as the dielectric voltage distribution inside the insulation is the same at different frequencies, and the ability to detect insulation failures is basically the same, the test can be achieved. Therefore, even if the frequency is wider than the power frequency range, it is acceptable. In the mid-1990s, in order to select the appropriate frequency range of the AC withstand voltage test, a lot of and careful basic research work was done. It is concluded that there is no significant difference in the breakdown characteristics of several typical insulation defects inside the rubber-plastic cable within the range of 30-300 Hz. This should be credible and has been widely adopted. The analysis and formation of this kind of good breakdown characteristics at different frequencies are mainly due to the excellent coaxial insulation structure, the single insulating medium, the relatively pure material, and the reasonable and regular electric field distribution. Therefore, the internal voltage distribution of the structure is the same at different frequencies, forming conditions for a wide frequency range test. Oil-paper insulated cables have been tested with a DC voltage with a frequency equal to zero. The actual effect is very good and has not been questioned for decades.
  
  (3) The third category is close to the power frequency, 35-75Hz
  
  Breakdown tests were performed on normal XLPE (cross-linked polyethylene) insulated cable samples abroad at different frequencies. The results show that the breakdown voltage is within 95% of the confidence level when the frequency is 35-75Hz. Therefore, some opinions agree that the test voltage frequency is best selected at 35-75Hz, which is also closer to the operating voltage frequency of 50Hz. It is worth noting that the above test result is a breakdown test for normal insulation. The test voltage value used in the handover and preventive tests is low, and it can only penetrate defective insulation weaknesses (mechanical damage, water branches, terminal head or joint box stress iron cone construction or material errors, etc. ), it is not enough to penetrate the normal insulation of the cable body. It can be seen that the purpose and working mechanism of the two tests are different. It seems unnecessary to “extend” the 35-75Hz breakdown characteristics of normal insulation to detect insulation defects.

Recommended products

AJ580 SF6 gas comprehensive tester

AJ580 SF6 gas comprehensive tester

AJHX800 Internet-based full-time high-voltage remote phasing system

AJHX800 Internet-based full-time high-voltage remote phasing system

AJ920 Rotor AC Impedance Tester

AJ920 Rotor AC Impedance Tester

AJVLF ultra low frequency high voltage generator

AJVLF ultra low frequency high voltage generator

AJ5000 Intelligent Insulation Resistance Tester

AJ5000 Intelligent Insulation Resistance Tester

AJHM Insulator Ash Density Tester

AJHM Insulator Ash Density Tester

AJ703 type microcomputer relay protection tester

AJ703 type microcomputer relay protection tester

Frequency conversion transformer comprehensive tester

Frequency conversion transformer comprehensive tester

RECOMMEND NEWS

2019
11-20
小黑点

The importance of quality in the wire and cable industry

  In order to better improve the good transmission of the power grid, the quality and integrity of the wire and cable industry play a vital role. In order to further improve the quality and integrity of the wire and cable industry, safeguard the legitimate rights and interests of the industry, and promote the healthy development of the wire and cable industry and market prosperity, the relevant state quality and technical supervision departments have specially formulated the wire and cable industry regulations.
查看详情
2019
11-20
小黑点

State Grid announces distributed photovoltaic construction capacity

In order to avoid the good development of distributed photovoltaic power generation projects, the State Grid adopts the method of prior investment subsidies for photovoltaic power generation projects, which may indeed cause the problem of construction but not use. As far as State Grid Corporation of China is concerned, we encourage customers to generate more electricity by actively implementing the measures of surplus electricity grid connection and full purchase.   
查看详情
2019
11-20
小黑点

China's nuclear power technology enters the international advanced ranks

  As the China Experimental Fast Reactor project passed the acceptance by experts of the scientific and technological organization department, it marked that China's nuclear power technology officially joined the international advanced ranks. Fast reactor has the characteristics of high utilization rate of uranium resources, transmutation of nuclear waste and high safety. It is the preferred reactor type for the fourth-generation advanced nuclear energy system in the world and represents the development direction of the fourth-generation nuclear energy system. The China Experimental Fast Reactor has a thermal design power of 65 MW and an electric power of 20 MW. It is currently one of the few high-power and power-generating experimental fast reactors in the world. Its main system settings and parameter selection are the same as those of large fast reactor power plants.
查看详情
2019
11-20
小黑点

Promote the construction of smart grid and help the development of the photovoltaic industry

  At present, photovoltaic products cannot be opened in the Chinese market. The main reason is that my country's power grid has limited acceptance of new energy sources such as solar and wind power. To solve this problem, my country urgently needs to develop a strong smart grid.
查看详情
2019
11-20
小黑点

Strengthen the supervision of the quality of wire and cable products

  Wires and cables are indispensable basic equipment for the transmission of electric energy, the transmission of information, and the manufacture of various motors, electrical appliances, meters, automobiles, machine tools and other equipment. In order to strengthen product quality supervision and safeguard the interests of consumers, relevant departments have recently issued Carry out quality inspection activities and find that all problems are exposed.
查看详情
2019
11-20
小黑点

Continue to improve the level of intelligent construction of rural networks

  In order to implement the overall arrangements for the construction of smart grids, seize the opportunity for the country's new round of rural power grid transformation and upgrade, and accelerate the construction of a new rural power grid based on strength and intelligence, it is the new target and task of the State Grid Corporation's rural power work, and it is also a realization It is an inevitable requirement for the coordinated development of rural power grids and power grids at all levels. Each power communication network is an important foundation for advancing the intelligent construction of rural power grids and ensuring the production, operation, management and power supply services of the power grid. In recent years, power supply companies at all levels of the State Grid System have done a lot of work in this area and achieved certain results. However, some units are inaccurate in the construction and technical direction of the power communication network, and the construction mode, equipment level, and application effect of the power communication network in different regions and counties are quite different; the construction of each power communication network lacks system planning, and the overall level lags behind the agricultural Conditions such as electricity development requirements still exist, which are not compatible with the development of a strong smart grid. The task of strengthening and perfecting the construction of various power communication networks in the power grid system is very urgent.
查看详情

SAUNDERS

WRITE A MESSAGE TO US

Username used for comment:
客户留言
Description:
武汉港联电气成套设备有限公司

Contact number

Add:Room 01, 3 / F, building 4, daijiashan science and Technology City, 888 Hanhuang Road, Jiang'an District, Wuhan City