AJ703 type microcomputer relay protection tester
Product description
Parameters
Chapter One Device Features and Technical Parameters
Section One Main Features
Standard 4-phase voltage and 3-phase current output With 4-phase voltage and 3-phase current output, it is convenient to carry out various combination outputs for various types of protection tests. The single-phase voltage can output up to 120V, the single-phase current can output up to 40A (10 seconds), the current three can output 120A, the fourth phase voltage Ux is a multi-function voltage item, which can be set to 4 types of 3U0 or check the same voltage, or Output at any voltage value.
The single machine is easy to operate. The single machine is operated by a convenient and flexible rotating mouse through the large-screen LCD display, all displayed in Chinese. It can complete most of the field test and verification work, can verify various relays and microcomputer protections, and can simulate various complex transient, permanent, and conversion faults for a whole set of tests. It can be used after booting, and the operation is convenient and quick.
Dual operation mode, connected to the computer and running through a full set of Chinese operating software on the Windows platform, can perform various large-scale, complex and more automated calibration tasks, can easily test and scan various protection settings, and can store and test in real time Data, display vector diagrams, draw fault waveforms, print reports online, etc.
The software has powerful functions and can complete various large-scale and complex calibration tasks with a high degree of automation, such as three-phase differential test, factory power quick-cutting, automatic switch-on test, line protection inspection and simultaneous reclosing, etc. It can easily test and scan various Protect the fixed value, perform fault playback, store test data in real time, display vector diagrams, and print reports online.
Rich switch contacts Three-phase 7-way contact input and 2 pairs of empty contact output. The input contacts are empty contacts and compatible with 0~250V potential contacts, which can be intelligently and automatically identified. The input and output contacts can be expanded according to user needs.
Large-screen LCD display This machine adopts a 320×240 dot matrix large-screen high-resolution graphic LCD display. All operation processes are set on the display. The operation interface and test results are displayed in Chinese, and the display is intuitive and clear.
Self-protection It adopts a reasonably designed heat dissipation structure, and has a variety of reliable and complete protection measures, soft start of the power supply, and certain fault self-diagnosis and blocking functions.
has an independent dedicated DC power output The device has a 110V and 220V dedicated DC power output.
High performance-price ratio It is a cross-professional joint design product that integrates advanced scientific and technological achievements from multiple disciplines. It combines the performance of a large-scale tester and the price of a small-scale tester, and has a high performance-price ratio.
Section 2 Rated Parameters
AC current output
Output accuracy 0.2 level
Phase current output (effective value) 0~40A
Triple parallel current output (effective value) 0~120A
Long-term allowable working value of phase current (effective value) 10A
Phase current maximum output power 420VA
The maximum output power at the maximum output of triple parallel current is 900VA
Three parallel current maximum output allowable working time 10s
Frequency range (fundamental wave) 20~1000Hz
Harmonic order 1~20th
DC current output
Output accuracy 0.2 level
Current output 0~±10A / each phase, 0~±30A / triple parallel
Maximum output load voltage 20V
AC voltage output
Output accuracy 0.2 level
Phase voltage output (effective value) 0~120V
Line voltage output (effective value) 0~240V
phase voltage/line voltage output power 80VA / 100VA
Frequency range (fundamental wave) 20~1000Hz
Harmonic order 1~20th
DC voltage output
Output accuracy 0.2 level
Phase voltage output amplitude 0~±160V
Line voltage output amplitude 0~±320V
Phase voltage/line voltage output power 70VA / 140VA
switch and time measurement
|
Three phase
|
Remarks
|
Switch input
|
7 way
|
Empty contact: 1~20mA, 24V
Potential contact access: "0": 0~ +6V; "1": +11 V~ +250V
|
Switch output
|
2 pairs
|
DC:220V/0.2A;AC:220V/0.5A
|
Time measurement
|
Measuring range 0.1ms ~ 9999s, measuring accuracy 0.1mS
|
volume and weight
|
Three phase
|
Dimensions
|
400×300×180mm³
|
Stand-alone weight
|
22kg
|
Power supply
|
AC 220V±10%,50/60Hz
|
Ambient temperature
|
-10℃~ +50℃
|
Scan the QR code to read on your phone
Previous
None
Next
None
Related products
WRITE A MESSAGE TO US
Explanation of Enquiry
Contact information
Basic information
Method of contact and occupation
Company information
Contact number
Add:Room 01, 3 / F, building 4, daijiashan science and Technology City, 888 Hanhuang Road, Jiang'an District, Wuhan City